SCHNEIDER HT SWITCHGEAR
📍Manufactured in Chennai, Tamil Nadu, India
<p> </p> <p><strong>Ratings</strong> </p> <p><strong>Technical Overview</strong></p> <table border="0" cellpadding="1" cellspacing="1" style="width:100%"> <tbody> <tr> <td><strong>Type</strong> </td> <td>PIX-36</td> </tr> <tr> <td><strong>Rated Voltage</strong></td> <td>upto 36kV</td> </tr> <tr> <td><strong>Rated Continuous Current </strong></td> <td>upto 2500 A</td> </tr> <tr> <td><strong>Rated Frequency</strong></td> <td>50 Hz</td> </tr> <tr> <td><strong>Rated Interrupting Current </strong></td> <td>upto 26.3 kA</td> </tr> <tr> <td><strong>Rated Making Current </strong></td> <td>upto 66 kAp</td> </tr> <tr> <td><strong>Rated Short Time Current</strong></td> <td>upto 26.3 kA for 3 sec.</td> </tr> <tr> <td><strong>Operating Duty</strong></td> <td>O-0.3 sec-CO-3min-CO</td> </tr> <tr> <td><strong>Applicable Standards</strong></td> <td>IEC 62271-100 / 200 & IEC 62271-1</td> </tr> <tr> <td><strong>Power Frequency Withstand Voltage</strong></td> <td>70 kV</td> </tr> <tr> <td><strong>Impulse Withstand Voltage</strong></td> <td>170 kVp</td> </tr> <tr> <td><strong>Degree Of Protection</strong></td> <td>IP4X as per IEC 60529</td> </tr> <tr> <td><strong>Type Of Mechanism</strong></td> <td>Motor charged, Stored energy, Spring operated</td> </tr> <tr> <td><strong>Rated Single Capacitor Bank</strong></td> <td>400A</td> </tr> <tr> <td><strong>Rated Cable Charging Current</strong></td> <td>25A</td> </tr> <tr> <td><strong>Rated Line Charging Current</strong></td> <td>10A</td> </tr> </tbody> </table> <p><br /> </p>